Once you have received your login to the Voonami Customer Portal, you are able to enable Data Center access for your team. Please follow the steps found here.
If you are colocating at our Orem (slc1) Data Center, each person requiring access to the Data Center will need to setup their Access Card at the West Valley (slc2) Data Center.
Voonami does not provide PDU’s. Please contact our support team to coordinate a time for them to meet you to plug in your power. |
Power | The Outlet Voonami Provides | The Plug required on the PDU |
---|---|---|
120/15 | NEMA L5-15R | NEMA L5-15P |
120/20 | NEMA L5-20R | NEMA L5-20P |
120/30 | NEMA L5-30R | NEMA L5-30P |
208/20 | NEMA L6-20R | NEMA L6-20P |
208/30 | NEMA L6-30R | NEMA L6-30P |
208/30 (3 phase) | NEMA L21-30R | NEMA L21-30P |
208/50 (3 phase) | Hubbell CS8369 | Hubbell CS8365C (This is a 208 volt 50 amp California Style Plug) |
This information will be delivered to you via email once we have finalized the setup of your order. Please keep an eye out for this!
The majority of our full and half cabinets are APC NetShelter SX
42U 600mm wide x 1070mm deep) enclosures with side panels.
Rack Width: 19"
Maximum Mounting Depth: 36.02inches(915.0mm, 91.49cm)
When you are ready to setup your cabinet and connect your power, please contact our support team to schedule a time.